倍加福KFU8-GUT-EX1.D报警设定器

有效期: 2020-08-05

数量(件) 价格(元/件)
168 168.00元/件
  • 最小起订: 1件
  • 发货地址: 上海 宝山区
  • 发布日期:2019-08-05
  • 访问量:394
咨询电话:131-2792-5599
详细参数
品牌倍加福型号KFU8-GUT-EX1.D
类型安全栅加工定制
安装方法导轨安装传输精度0.1,
输出负载详见参数适用范围热电阻,热电偶,电位计,电压输入
规格详见参数产地其他

产品详情

倍加福KFU8-GUT-EX1.D报警设定器简介


•1通道隔离屏障

•适用于不同电源

•热电偶、RTD、电位器或电压输入

•冗余TC输入

•电流输出0/4 mA…20mA

•2继电器触点输出

•可通过PACTware或键盘配置

•线路故障(LFD)和传感器烧毁检测

•根据iec61508 / iec61511,安全等级可达SIL2


应用

这种隔离屏障用于内在安全应用。该装置转换电阻温度计的信号,a的热电偶、电位器或电压源输出电流成比例。它还提供一个中继行程值。可移动终端块K-CJC-**可用作附件用于内部冷端补偿热电偶。故障由led acc进行信号处理。到那慕尔NE44。使用PACTware可以很容易地配置该设备配置软件。


技术参数



General specifications

Signal type Analog b

Functional safety related beters

Safety Integrity Level (SIL) SIL 2

Supply

Connection terminals 23, 24

Rated voltage Ur 20 ... 90 V DC / 48 ... 253 V AC

Power dissipation/power consumption ≤ 2 W ; 2.5 VA / 2.2 W ; 3 VA

Interface

Programming interface programming socket

Input

Connection side field side

Connection terminals 1, 2, 3, 4, 6

RTD Pt100, Pt500, Pt1000, Ni100, Ni1000

Types of measuring 2-, 3-, 4-wire technology

Lead resistance ≤ 50 Ω

Measurement loop monitoring sensor breakage, sensor short-circuit

Thermocouples type B, E, J, K, L, N, R, S, T (IEC 584-1: 1995)

Cold junction compensation external and internal

Measurement loop monitoring sensor breakage

Potentiometer 0.8 ... 20 kΩ

Types of measuring 2-, 3-, 5-wire technology

Voltage 0 ... 10 V , 2 ... 10 V , 0 ... 1 V , -100 ... 100 mV

Input resistance ≥ 250 kΩ (0 ... 10 V)

≥ 1 MΩ (0 ... 1 V, -100 ... 100 mV)

Measuring current approx. 400 µA with resistance measuring sensor

Output

Connection side control side

Connection output I: terminals 10, 11, 12

output II: terminals 16, 17, 18

output III: terminals 8+, 7-

Output I, II relay

Contact loading 250 V AC / 2 A / cos φ ≥ 0.7 ; 40 DC / 2 A

Mechanical life 5 x 107 switching cycles

Energized/De-energized delay approx. 20 ms / approx. 20 ms

Output III Analog current output

Current range 0 ... 20 mA or 4 ... 20 mA

Open loop voltage ≤ 24 V DC

Load ≤ 650 Ω

Fault signal downscale I ≤ 3.6 mA, upscale I ≥ 21 mA (acc. NAMUR NE43)

Transfer characteristics

Deviation

Temperature effect Input: 0.005 %/K (50 ppm) of span ; current output: 0.005 %/K (50 ppm) of span

RTD ≤ 0.2 % of span

Thermocouples max. 10µV

deviation of CJC: ±0.8 K

Voltage 0.1 % of span

Potentiometer 0.1 % of span when < 5 kΩ

0.5 % of span when > 5 kΩ

Current output ≤ 20 µA

Sampling rate approx. 700 ms